K260 & K340
Please note that this product is no longer available and the information below is for reference only.
Keston Boilers have launched
two commercial condensing gas boilers to further
extend our existing range of ultra-high efficiency
domestic and commercial boilers.
The Keston 260 (76kW) output and Keston 340 (100kW) output are unique in concept and design and each have an exceptionally high efficiency at 98% gross.
Despite their powerful output, the
boilers are designed to be wall mounted, though floor
standing installation can be accommodated by using
the optional floor standing frame. The compact size
means the new Keston boilers can be sited practically
anywhere without the need for a dedicated boiler
room.
Each model comprises two boiler modules with individual gas valves, fans, burners and heat exchanger assemblies. Each module operates completely independently and is automatically sequenced to offer optimum load matching.
Firing sequence is regularly rotated automatically to even usage levels.
Unique Flue System
All Keston boilers have the advantage of a small diameter plastic flue system and the two new models are no exception. The 100mm (4") diameter plastic flue can be extended up to 39 metres away from the unit, either vertically or horizontally, and can save thousands of pounds on installation costs when compared to a conventional flue. In refurbishment projects there is no need for expensive re-lining of the flue. The system is also ideal for buildings with difficult flue options and particularly listed buildings with various restrictions.
An added benefit of the flue system is that the boilers can be sited practically anywhere and in the most convenient position.
How It Works
The Keston modules use a high powered combustion blower to deliver a pre-mix of gas and air to a downward firing burner in a high efficiency single pass heat exchanger. The heat exchanger is made from highly corrosion-resistant stainless steel formed into a tightly wound coil. Hot combustion gases from the burner pass through the coil providing heat to the water system.
Integral shunt pumps within the appliance cabinet ensure each module receives the correct water flow when firing.
The Keston boilers are of low mass and low water content giving a rapid response when there is a call for heat.
The design of Keston boilers, with
its single pass heat exchanger, avoids the complications
associated with other condensing boilers and, as
a result, does not need complicated printed circuit
boards. The unit is totally room sealed and requires
no ventilation to the room or compartment in which
it is installed for combustion air.
These two new boilers are exceptionally easy to install and maintain and include pipework header assemblies to assist speedy installation. They are completely environmentally sound with negligible NOx emissions of around 5ppm (parts per million) and can save up to 30% on the heating bill.
Practically any Heating Output
Because of its modular design, the
Keston lends itself to almost any required heating
output by way of multiple unit installations for
larger commercial or industrial applications, and
the benefits over a single commercial boilers are
immense. The Keston modular system is perfect for
decentralisation programs now happening in many commercial
installations,, such as hospitals and universities,
where one large commercial boiler is being replaced.
From initial purchase through to installation and maintenance, the Keston saves money, time and aggravation.
In most commercial applications, the
Keston modular system has proved to be far less expensive
to buy or install than the equivalent output single
commercial boiler.
The Highest Standards
All Keston boilers carry the CE Mark, are British Gas Approved and Service Listed and manufactured to ISO 9001 international certification.
The long life heat exchanger is made from exceptional quality high alloy stainless steel and carries a three year guarantee.
Technical Specification |
Keston 260
|
Keston 340
|
|
Max. Input (GCV) |
k/W/(Btu/h) |
84.6/(288,650) |
110.0/(375,300) |
Max. Output to Water (80/60C Flow/Return) |
k/W/(Btu/h) |
76.1/(259,650) |
99.0/(337,800) |
| Max. Output to Water (60/40C Flow/Return) |
k/W/(Btu/h) |
79.5/(271,250) |
104.0/(354,800) |
|
Max. Output to Water (50/30C Flow/Return) |
k/W/(Btu/h) |
82.9/(282,850) |
107.8/(367,800) |
|
Burner Press. - Hot (factory preset) |
mbar/(in w.g) |
9.8/(3.9) |
13.0/(5.2) |
|
Gas Consumption After 10 Mins. |
l/s / (ft³/hr) |
2.19/(278) |
2.84/(362) |
|
Max. Operating Flow Temp. |
°C |
80.0 |
80.0 |
|
Max. Head (Open Systems) |
m/(ft) |
30.5 |
30.5 |
|
Max. Press. (Sealed Systems) |
Bar |
2.70 |
2.70 |
|
Min. Head (Open Systems) |
m |
3.0 |
3.0 |
|
Required Inlet Gas Pressure (Dynamic) |
mbar/(in w.g) |
20.0/(8.0) |
20.0/(8.0) |
|
Recommended Temperature Differential |
°C |
10 to 15 |
10 to 15 |
| Required Water Flow Rate |
l/s |
1.60 |
2.00 |
| Integral Shunt Pump |
|
Yes |
Yes |
|
Electrical Supply |
|
230V 50Hz |
230V 50Hz |
|
Power Consumption - inc. pump (Max) |
W |
1200 |
1200 |
|
Cabinet Height |
mm |
1260 |
1260 |
|
Cabinet Width |
mm |
1080 |
1080 |
|
Cabinet Depth |
mm |
350 |
350 |
| Side Clearance |
mm |
1 |
1 |
| Base Clearance |
mm |
127 |
127 |
| Front
Clearence |
mm |
305 |
305 |
| Top Clearance |
mm |
127 |
127 |
| Weight - Full |
kg/(lbs) |
165/(363) |
165/(363) |
| Weight - Empty |
kg/(lbs) |
150/(330) |
150/(330) |
| Flow and Return Connections |
|
Rp 2"F |
Rp 2"F |
| Gas Connection |
|
Rp 1.25"F |
Rp 1.25"F |
| Condensate Connection |
|
22mm plastic overflow |
| Flue Pipe (nominal bore) |
mm/(in) |
100/(4) |
100/(4) |
| Air Intake Pipe Size (nominal bore) |
|
100/(4) |
100/(4) |
| Flue and Air Intake Material |
|
Keston Composite Pipe Only |
| Max. Air Intake length |
m |
20 |
20 |
| Max. Flue Outlet Length |
m |
39 |
39 |
| Max. Total Outlet and Air Intake Length |
m |
40 |
40 |
| Type of Gas |
|
G20 Natural Gas ONLY |
G20 Natural Gas ONLY |
| Optimum Flue Gas CO2 Level |
% |
8.4 |
8.4 |
|