The section below details the performance data for the Keston C90 and Keston C110 condensing boilers:

Technical Specification

C90

C110

Max. Input (GCV)

k/W/(Btu/h)

91.2 / (311,200)
113.0 / (385,600)

Max. Output (80/60C Flow/Return)

k/W/(Btu/h)

79.9 / (272,500)
99.4 / (339,400)
Max. Output (80/60C Secondary Flow/Return*)
k/W/(Btu/h)
40.3 / (137,600)
49.7 / (169,500)
Max. Output (50/30C Flow/Return)
k/W/(Btu/h)
89.8 / (306,800)
110.4 / (377,000)
Max. Output (50/30C Secondary Flow/Return*)
k/W/(Btu/h)
44.9 / (153,400)
55.2 / (188,500)
Min. Output (80/60C Flow/Return)

k/W/(Btu/h)

22.8 / (77,000)
25.0 / (83,500)
Min. Output (80/60C Secondary Flow/Return*)
k/W/(Btu/h)
11.3 / (38,500)
12.5 / (42,900)
Max Gas Consumption After 10 Mins.

l/s / (ft³/hr)

2.414 / (307)
2.992 / (380)
Max. Operating Flow Temp.

°C

82.0
82.0
Max. Head (Open Systems)

m/(ft)

30.5
30.5
Max. Press. (Sealed Systems)
Bar
2.70
2.70
Min. Head (Open Systems)

m

3.0
3.0
Required Inlet Gas Pressure (Dynamic)

mbar/(in w.g)

20.0 / (8.0)
20.0 / (8.0)
Flow/Return Temperature Differential

°C

10 to 20
10 to 20
Electrical Supply

 

230V 50Hz
230V 50Hz
Power Consumption (Standby)
W
8
16
Power Consumption (Max)

W

260
520
IP Rating
 
IP20
IP20
Cabinet Height

mm

825
825
Cabinet Width

mm

1000
1000
Cabinet Depth

mm

337
337
Side Clearance
mm 
25
25
Base Clearance
mm 
150
150
Front Clearence
 mm
300
300
Top Clearance
mm 
150
150
Weight - Full
kg
143
143
Weight - Empty
kg
125
125
Flow and Return Connections
 
Rp 1.5" F
Rp 1.5" F
Secondary Flow/Return Connections
 
Rp 1" F
Rp 1" F
Gas Connection
 
Rp 1" F
Rp 1" F
Condensate Connection
 
 22mm plastic overflow
Flue/Air Intake Pipe Size(nominal bore)
mm/(in)
100(4)
100(4)
Flue and Air Intake Material
 
Keston Composite Pipe Only
Max. Air Intake length
m
30
30
Max. Flue Outlet Length
m
30
30
Type of Gas
 
G20 Natural Gas ONLY
G20 Natural Gas ONLY
Optimum Flue Gas CO2 Level
%
8.3
8.8

NB: *These are not in addition to main flow outputs.

 

 
""